Pipe Design
TITANUS
SUPER·SENS
®
4 –
30
Data: 02/09
TSS_04_A-en-e
4.3.2.3 M-pipe
system
TITANUS
®
d
TITANUS
®
Fig. 4.13: M-pipe system, such as for equipment protection
Limit values
Min. distance from TITANUS
®
to 1st sampling aperture
2 m
Max. distance from TITANUS
®
to 1st sampling aper-
ture
10 m
Max. distance from the 1
st
sampling aperture to the
last sampling aperture
6 m
Max. overall pipe length Ø 25 mm
20 m
Max. number of aspiration apertures (n) per pipe sys-
tem
15 pcs.
Minimum distance between aspiration apertures (d)
0,5 m
Maximum distance between aspiration apertures (d)
4 m
Aspiration apertures
Number of aper-
tures
3 6 9 12
15
∅
of all aspiration
apertures in mm
17F
18
) 6,0 4,2 3,6 3,0 2,5
18
Press cut diameter in aspiration-reducing film sheet