8.5 Exchange of the air flow sensor filter
Fig. 8.2: Exchange of the air flow sensor filter
Open TITANUS
®
by loosening the four screws on the housing lid.
Then open the lid carefully.
Detach the cable of the display board from the base board (X6).
Now the lid can be removed.
Detach both hose ends from the air flow sensor filter
and take
it out
.
Fix again both hose ends onto the new air flow sensor filter.
Fix the cable of the display board onto the base board.
Close the housing lid and fasten the four screws tightly.
Avoid mechanical load on the air flow sensor filter!.
ATTENTION