Commissioning
TSS_07_A-en-e Data:
02/09
7
– 7
7.5 Operational check of
TITANUS
®
If it is not possible to adjust TITANUS
®
check the functionality by means
of the testing pipe and a digital manometer or the diagnostic device. Dur-
ing this check TITANUS
®
is to be operated.
7.5.1 Preparation of the operational check
Set the switches on the base board (refer to
2H
Fig. 7.3) according to
the following table:
Switch base board
air flow monitoring
Switch S2
Contact A (1)
Contact A (1)
Contact A (1)
Contact A (1)
off on off off
delay period
0.5 min
activating threshold
large
Switch base board
detector sensitivity
Switch S2
Contact E (5)
Contact F (6)
Contact E (7)
Contact F (8)
on off off on
alarm/delay period
10 s
response sensitivity (HA) 0.1%/m
Switch base board
fault signal
Switch S2
Contact J (10)
off
non-latched
Remove the pipe system from TITANUS
®
.