41
Condensate drain
When the condensate collection tank is full, the drain pump switches on automatically for 70 s and the corresponding
sensor checks the level. A locking alarm is displayed if the condensate level does not fall within the pre-set time. After
having checked the discharge pipe and resolved the drain lock, you can reset the error and the device will resume operation
(answer "YES" on "UNLOCK").
T ext Probe
A fault on the external temperature sensor generates this non-locking error (only the heat pump locks). After having
resolved the problem (through Technical Service intervention), you can reset the error (answer "YES" for "CALL
SERVICE").
NOTE: the system does not automatically call Technical Service.
SETUP
You can access the Date and Hour setting and weekly programming with this option
ENGLISH
F
MAIN MENU
USE MENU
ALARM
SETUP
F
ALARM
CHECK
TUBE
UNLOCK? YES
F
MAIN MENU
USE MENU
ALARM
SETUP
F
ALARM
EXT PROBE
CALL
SERVICE YES
F
MAIN MENU
ALARM
SETUP
INFO
F
SETUP
DATE&HOUR
PROGRAM
USE MENU