7.2.2 Application Setups
The application setups menu makes it easy to configure the MCD 500 for common applications. The MCD 500 selects the
parameters relevant to the application and suggests a typical setting, and you can adjust each parameter to suit your exact
requirements.
On the display the highlighted values are suggested values and the values indicated by a
▶
are the loaded values.
Always set
1-1 Motor FLC
to match the motor's nameplate full load current. The suggested value for motor FLC is the
starter's minimum FLC.
Pump Centrifugal
Suggested Value
Compressor Recip
Suggested Value
Motor Full Load Current
Motor Full Load Current
Start Mode
Adaptive Start Profile
Start Ramp Time
Stop Mode
Adaptive Stop Profile
Stop Time
Adaptive Control
Early Acceleration
10 seconds
Adaptive Control
Late Deceleration
15 seconds
Start Mode
Start Ramp Time
Current Limit
Constant Current
10 seconds
450%
Pump Submersible
Conveyor
Motor Full Load Current
Motor Full Load Current
Start Mode
Adaptive Start Profile
Start Ramp Time
Stop Mode
Adaptive Stop Profile
Stop Time
Adaptive Control
Early Acceleration
5 seconds
Adaptive Control
Late Deceleration
5 seconds
Start Mode
Start Ramp Time
Current Limit
Stop Mode
Adaptive Stop Profile
Stop Time
Constant Current
5 seconds
400%
Adaptive Control
Constant Deceleration
10 seconds
Fan Damped
Crusher Rotary
Motor Full Load Current
Motor Full Load Current
Start Mode
Current Limit
Constant Current
350%
Start Mode
Start Ramp Time
Current Limit
Excess Start Time
Locked Rotor Time
Constant Current
10 seconds
400%
30 seconds
20 seconds
Fan Undamped
Crusher Jaw
Motor Full Load Current
Motor Full Load Current
Start Mode
Adaptive Start Profile
Start Ramp Time
Excess Start Time
Locked Rotor Time
Adaptive Control
Constant Acceleration
20 seconds
30 seconds
20 seconds
Start Mode
Start Ramp Time
Current Limit
Excess Start Time
Locked Rotor Time
Constant Current
10 seconds
450%
40 seconds
30 seconds
Compressor Screw
Motor Full Load Current
Start Mode
Start Ramp Time
Current Limit
Constant Current
5 seconds
400%
Table 7.4
Programming
MCD 500 Operating Instruction
52