4.9.2 Bussman Fuses - Square Body (170M)
Model
SCR I
2
t (A
2
s)
Supply Voltage
(
≤
440 VAC)
Supply Voltage
(
≤
575 VAC)
Supply Voltage
(
≤
690 VAC)
MCD5-0021B
1150
170M1314
170M1314
170M1314
MCD5-0037B
8000
170M1316
170M1316
170M1316
MCD5-0043B
10500
170M1318
170M1318
170M1318
MCD5-0053B
15000
170M1318
170M1318
170M1318
MCD5-0068B
15000
170M1319
170M1319
170M1318
MCD5-0084B
512000
170M1321
170M1321
170M1319
MCD5-0089B
80000
170M1321
170M1321
170M1321
MCD5-0105B
125000
170M1321
170M1321
170M1321
MCD5-0131B
125000
170M1321
170M1321
170M1321
MCD5-0141B
320000
170M2621
170M2621
170M2621
MCD5-0195B
320000
170M2621
170M2621
170M2621
MCD5-0215B
320000
170M2621
170M2621
170M2621
MCD5-0245C
320000
170M2621
170M2621
170M2621
MCD5-0360C
320000
170M6010
170M6010
170M6010
MCD5-0380C
320000
170M6011
170M6011
-
MCD5-0428C
320000
170M6011
170M6011
-
MCD5-0595C
1200000
170M6015
170M6015
170M6014
MCD5-0619C
1200000
170M6015
170M6015
170M6014
MCD5-0790C
2530000
170M6017
170M6017
170M6016
MCD5-0927C
4500000
170M6019
170M6019
170M6019
MCD5-1200C
4500000
170M6021
-
-
MCD5-1410C
6480000
-
-
-
MCD5-1600C
12500000
170M6019*
-
-
Table 4.18
* Two parallel connected fuses required per phase.
Electrical Installation
MCD 500 Operating Instruction
MG17K402 - VLT
®
is a registered Danfoss trademark
23
4
4