6 Operation
6.1 Operation and LCP
6.1.1 Operating Modes
In Hand On mode:
•
To soft start the motor, press [Hand On] on the
LCP
•
To stop the motor, press [Off] on the LCP
•
To reset a trip on the starter, press [Reset] on the
LCP
•
To emergency stop the motor, press the local
[Off] and [Reset] buttons at the same time. The
soft starter will remove power from the motor
and open the main contactor, and the motor will
coast to stop. Emergency stop can also be
controlled via a programmable input.
In Auto On mode:
•
To soft start the motor, activate the Start remote
input
•
To stop the motor, activate the Stop remote
input
•
To reset a trip on the starter, activate the Reset
remote input
NOTE
Brake and Jog functions operate only with in-line
connected motors (see Inside Delta Operation)
6.1.2 The LCP
1
7
7
H
A
3
8
3
.1
0
3
4
5
2
1
®
Illustration 6.1
1
Four-line display for status and programming details.
2
Display control buttons:
Status: Return to the status displays
Quick Menu: Open the Quick Menu
Main Menu: Open the Main Menu
Alarm Log: Open the Alarm Log
3
Menu navigation buttons:
[Back]: Exit the menu or parameter, or cancel a
parameter change
[OK]: Enter a menu or parameter, or save a parameter
change
[
▲
] [
▼
]: Scroll to the next or previous menu or
parameter, change the setting of the current
parameter or scroll through the status screens.
4
Soft starter local control buttons:
[Hand On]: Start the motor and enter local control
mode.
[Off]: Stop the motor (only active in Hand On mode).
[Auto On]: Set the starter to Auto On mode.
[Reset]: Reset a trip (Hand On mode only).
5
Remote input status LEDs.
Table 6.1
6.2 Remote Mounted LCP
A remote mounted LCP can be installed with the MCD 500.
The Control Panel LCP501 can be mounted up to 3 metres
away from the starter, for control and monitoring.
Operation
MCD 500 Operating Instruction
46
MG17K402 - VLT
®
is a registered Danfoss trademark
6
6