4.2.2 In-line Installation
4.2.2.1 In-line Installation, Internally
Bypassed
1
77
H
A
4
3
0
.1
1
M
3
6/T3
2/T1
5/L3
3/L2
1/L1
13
14
4/T2
E
KM1
KM1
F1
Illustration 4.4
KM1
Main contactor (optional)
F1
Fuses (optional)
Table 4.5
4.2.2.2 In-line Installation, Non-bypassed
1
7
7
H
A
4
2
9
.1
1
6/T3
2/T1
5/L3
3/L2
1/L1
13
14
4/T2
E
KM1
KM1
F1
M
3
Illustration 4.5
KM1
Main contactor (optional)
F1
Fuses (optional)
Table 4.6
4.2.2.3 In-line Installation, Externally
Bypassed
Non-bypassed models have dedicated bypass terminals,
which allow the soft starter to continue providing
protection and monitoring functions even when bypassed
via external contactor. The bypass contactor must be
connected to the bypass terminals and controlled by a
programmable output configured to Run (see parameters
4.1 thorugh 4.9).
NOTE
The bypass terminals on MCD5-0245C are T1B, T2B, T3B.
The bypass terminals on MCD5-0360C ~ MCD5-1600C are
L1B, L2B, L3B.
NOTE
The fuses can be installed on the input side if required.
177HA6
17
.10
M
3
F1
6/T3
2/T1
5/L3
3/L2
1/L1
13
14
4/T2
E
KM1
KM1
T1B
T2B
T3B
KM2
34
33
KM2
Illustration 4.6 MCD5-0245C
KM1
Main contactor
KM2
Bypass contactor (external)
F1
Semiconductor fuses (optional)
Table 4.7
Electrical Installation
MCD 500 Operating Instruction