5.9 Installation with Bypass Contactor
The MCD 500 is installed with a bypass contactor (AC1 rated). The bypass contactor is controlled by the MCD 500 Run
Output which by default is assigned to Output Relay B (terminals 21, 22, 24).
KM1
24
VDC
22
21
13
14
24
33
34
06
05
08
07
17
18
25
11
16
A6
A5
A4
15
S1
S2
S3
E
+
+
6/T3
2/T1
4/T2
5/L3
3/L2
1/L1
L3B
L1B
L2B
KM1
F1
5
6
7
4
2
A
3
1
1
7
7
H
A
5
2
3
.1
0
Illustration 5.11
1
Control voltage (model dependent)
KM1
Bypass contactor
2
24 VDC output
F1
Semiconductor fuses (optional)
3
Remote control inputs
S1
Start contact
4
Motor thermistor input (PTC only)
S2
Stop contact
5
Relay outputs
S3
Reset contact
6
3-phase supply
13, 14
Relay output A
7
Motor terminals
21, 22, 24
Relay output B
33, 34
Relay output C
Table 5.12
Parameter settings:
•
4-4 Relay B Function
•
Select Run - assigns the run output function to Relay Output B (default value).
Application Examples
MCD 500 Operating Instruction
MG17K402 - VLT
®
is a registered Danfoss trademark
39