47
terminal board.
Warning:
If the power supply flexible line or the signal line of the equipment is damaged, only use special
flexible line to replace it.
1
、
Before connecting lines, read the voltages of the relevant parts on the nameplate. Then carry out
line connection according to the schematic diagram.
2
、
The air-conditioning unit shall have special power supply line which shall be equipped with
electricity leakage switch and air switch, so as to deal with overload conditions.
3
、
The air-conditioning unit must have grounding to avoid hazard owing to insulation failure.
4
、
All fitting lines must use crimp terminals or single wire. If multiple twisted wires are connected
to terminal board, arc may arise.
5
、
All line connections must conform to the schematic diagram of lines. Wrong connection may
cause abnormal operation or damage of the air-conditioning unit.
6
、
Do not let any cable contact the refrigerant pipe, the compressor and moving parts such as fan.
7
、
Do not change the internal line connections inside the air-conditioning unit. The manufacturer
shall not be liable for any loss or abnormal operation arising from wrong line connections.
8
、
shall not be liable for any loss or abnormal operation arising from wrong line connections.
H
、
Power Cable Connection
1. Air-conditioning unit with single-phase power supply
(
1
)
Remove the front-side panel of the outdoor unit.
(
2
)
Pass the cable though rubber ring.
(
3
)
Connect the power supply cable to the “L, N” terminals and
the grounding screw.
(
4
)
Use cable fastener to bundle and fix the cable.
2. Air-conditioning unit with 3-phase power supply
(
1
)
Remove the front-side panel of the outdoor unit.
(
2
)
Attach rubber ring to the cable-cross hole of the
outdoor unit.
(
3
)
Pass the cable though rubber ring.
(
4
)
Connect the power cable to the terminal and earthing
screws marked “L1, L2, L3 & N”.
Caution:
Take great care when carrying out the
following connections, so as to avoid
malfunction of the air-conditioning unit
because of electromagnetic interference.
(1) The signal line of the wire controller must
be separated from the power line and the
connecting line between the indoor unit and
the outdoor unit.
(2) In case the unit is installed in a place
vulnerable by electromagnetic interference, it
is better to use shielded cable or
double-twisted cable as the signal line of the
wire controller.
Caution:
For air-conditioner with auxiliary
heater, it is required to connect the
power cable to the “L1, L2 L3
“ terminals and the grounding screw.
Summary of Contents for ACP-18CC50GEI
Page 2: ......
Page 3: ...HR BiH Upute za uporabu RoHS ACP 18CC50GEI ACP 24CC70GEI ACP 36CC100GEI ...
Page 56: ......
Page 57: ...SR Korisničko uputstvo RoHS ACP 18CC50GEI ACP 24CC70GEI ACP 36CC100GEI ...
Page 110: ......
Page 111: ...CG Upute za uporabu RoHS ACP 18CC50GEI ACP 24CC70GEI ACP 36CC100GEI ...
Page 164: ......
Page 165: ...AL Udhëzime për përdorim RoHS ACP 18CC50GEI ACP 24CC70GEI ACP 36CC100GEI ...
Page 218: ......
Page 219: ...MAK Упатства за употреба RoHS ACP 18CC50GEI ACP 24CC70GEI ACP 36CC100GEI ...
Page 272: ......
Page 273: ...User manual ENG ACP 18CC50GEI ACP 24CC70GEI ACP 36CC100GEI RoHS ...
Page 274: ...1 1 Names and functions of parts A C P 1 8 C C 5 0 G E I A C P 2 4 C C 7 0 G E I ...
Page 275: ...2 A C P 3 6 C C 1 0 0 G E I ...
Page 276: ...3 2 Safety cautions Read the following carefully to assure safe use ...
Page 277: ...4 ...
Page 291: ...18 TIMER operation procedure ...
Page 293: ...20 How to inser t batteries ...
Page 296: ...23 6 Optimum operation ...
Page 298: ...25 The following are not troubles ...
Page 299: ...26 8 Installation notes ...
Page 300: ...27 9 Care and maintenance Please pull out the power plug after you used the air conditioner ...
Page 301: ...28 ...
Page 302: ...29 ...
Page 303: ...30 ...
Page 325: ...52 70 C The installation altitude beyond the hight of 1000m ...
Page 326: ...53 ...
Page 327: ......
Page 331: ...3 4 ...
Page 334: ...3 4 ...
Page 342: ...3 4 3 4 3 4 ...
Page 343: ......
Page 344: ......
Page 345: ......