3.7.3.1. Monitor 1 Input Port Setting
Set when connecting an external contact to DM0. (When
using a motor lock, set to 1 or 2.)
Default Setting: ‘0.None’
-
‘0.None’: When nothing is connected
-
‘1.NO’ or ‘2.NC’: When the open door status monitoring pin is connected
-
‘3.Fire NO’ or ‘4.Fire NC’: When the fire detection sensor is connected
-
‘5.Panic NO’ or ‘6.Panic NC’: When the panic situation detection sensor is connected
-
‘7.EMC NO’ or ‘8.EMC NC’: When the emergency detection sensor is connected
-
‘9.Ctrler Out’: When the authentication result is sent to the external controller
(Connect the REDled of controller to DM0 or DM1 through the board toward TR. Set the
relevant pin to ‘9.Ctrler Out’. WiegandOut must be set.)
Press [ENT] button to move to the next setting.
3.7.3.2. Monitor 2 Input Port Setting
Set when connecting an external contact to DM1. (When
using a motor lock, set to 1 or 2.)
Default Setting: ‘0.None’
-
‘0.None’: When nothing is connected
-
‘1.NO’ or ‘2.NC’: When the open door status monitoring pin is connected
-
‘3.Fire NO’ or ‘4.Fire NC’: When the fire detection sensor is connected
-
‘5.Panic NO’ or ‘6.Panic NC’: When the panic situation detection sensor is connected
-
‘7.EMC NO’ or ‘8.EMC NC’: When the emergency detection sensor is connected
-
‘9.Ctrler Out’: When the authentication result is sent to the external controller
(Connect the REDled of controller to DM0 or DM1 through the board toward TR. Set the
relevant pin to ‘9.Ctrler Out’. WiegandOut must be set.)
After selecting the set value, press [ENT] button, and the screen will go to the upper menu.