Error code Description
80F0h
Wrong checksum in respond
80FEh
Wrong start sign in respond
80FFh
Wrong slave address in respond
9000h
Buffer overflow (no data send)
9001h
Data too long (>1024byte)
9002h
Data too short (<2byte)
Modbus RTU/ASCII Master
Error code Description
2000h
Send ready (positive slave respond)
2001h
Send ready (negative slave respond)
8080h
Receive buffer overflow (no space for receipt)
8090h
Acknowledgement delay time exceeded
80F0h
Wrong checksum in respond
80FDh
Length of respond too long
80FEh
Wrong function code in respond
80FFh
Wrong slave address in respond
9000h
Buffer overflow (no data send)
9001h
Data too long (>1024byte)
9002h
Data too short (<2byte)
VIPA System 300S
Deployment PtP communication
Communication > FC/SFC 217 - SER_SND
HB140 | CPU-SC | 312-5BE13 | GB | 15-50
149