Status indication X11: DI
n
1L+
– LED (green)
Supply voltage available for DI
n
.0 ... .7
– LEDs (green)
I+0.0 ... I+0.7
I+1.0 ... I+1.7
Starting with ca. 15V the signal "1" at the input is recognized
and the according LED is activated
6.6.3 Parameterization
1.
Start the Siemens SIMATIC Manager with your project and open
the hardware configurator.
2.
Place a profile rail.
3.
Configure on slot 2 the Siemens CPU 312C (6ES7
312-5BE03-0AB0 V2.6).
4.
Open the dialog window "Properties" by a double click to the
Count
submodule of the CPU.
5.
As soon as you select the operating mode "Frequency measure-
ment" to the corresponding channel, a dialog window for the fre-
quency measurement is created and displayed and filled with
default parameters.
6.
Execute the wished parameterization.
7.
Store the project with
‘Station
è
Save and compile’
.
8.
Transfer the project to the CPU.
In the following the parameters are listed which may be used for fre-
quency measurement configuration during hardware configuration.
Parameters, which are not listed here, are ignored by the CPU.
n
General
Here the short description of the counter function may be found.
At Comment information about the module such as purpose may
be entered.
n
Addresses
Here the start address of the counter function is set.
Parameter overview
VIPA System 300S
Deployment I/O periphery
Frequency measurement > Parameterization
HB140 | CPU-SC | 312-5BE13 | GB | 15-50
122