Sub
module
Default
address
Access
Assignment
776
DInt
reserved
780
DInt
reserved
Output area
Sub
module
Default
address
Access
Assignment
DI10/DO6
124
Byte
Digital output Q+0.0 ... Q+0.7
Counter
768
DWord
reserved
772
DWord
reserved
776
DWord
reserved
780
DWord
reserved
5.5 Hardware configuration - CPU
The configuration of the CPU takes place at the Siemens
‘hardware
configurator’
. The hardware configurator is part of the Siemens
SIMATIC Manager. It serves for project engineering. The modules,
which may be configured here are listed in the hardware catalog. If
necessary you have to update the hardware catalog with
‘Options
è
Update Catalog’
.
For project engineering a thorough knowledge of the Siemens
SIMATIC Manager and the Siemens hardware configurator is
required.
Please consider that this SPEED7-CPU has 4 ACCUs.
After an arithmetic operation (+I, -I, *I, /I, +D, -D, *D, /D,
MOD, +R, -R, *R, /R) the content of ACCU 3 and ACCU 4
is loaded into ACCU 3 and 2. This may cause conflicts in
applications that presume an unmodified ACCU 2.
For more information may be found in the manual "VIPA
Operation list SPEED7" at "Differences between SPEED7
and 300V programming".
To be compatible with the Siemens SIMATIC Manager the following
steps should be executed:
1.
Start the Siemens hardware configurator with a new project.
2.
Insert a profile rail from the hardware catalog.
3.
Place at
‘Slot’
number 2 the CPU 312C (6ES7
312-5BE03-0AB0 V2.6).
Precondition
Proceeding
VIPA System 300S
Deployment CPU 312-5BE13
Hardware configuration - CPU
HB140 | CPU-SC | 312-5BE13 | GB | 15-50
49