Byte
Bit 7...0
0
n
Bit 0: set at module failure
n
Bit 1: 0 (fix)
n
Bit 2: set at external error
n
Bit 3: set at channel error
n
Bit 7 ... 4: 0 (fix)
1
n
Bit 3 ... 0: Module class
– 0101b: Analog
– 1111b: Digital
n
Bit 4: Channel information present
n
Bit 7 ... 5: 0 (fix)
2
00h (fix)
3
00h (fix)
The record set 0 of the counter function, frequency meas-
urement and pulse width modulation has the same struc-
ture. There are differences in the structure of record set 1.
The record set 1 contains the 4byte of the record set 0 and addition-
ally 12byte module specific diagnostic data. The diagnostic bytes
have the following assignment:
Byte
Bit 7...0
0 ... 3
4
n
Bit 6 ... 0: Channel type (here 70h)
– 70h: Digital input
– 71h: Analog input
– 72h: Digital output
– 73h: Analog output
– 74h: Analog input/output
n
Bit 7: More channel types present
– 0: no
– 1: yes
5
Number of diagnostic bits per channel (here 08h)
6
Number of channels of a module (here 08h)
7
n
Bit 0: Error in channel group 0 (I+0.0 ... I+0.3)
n
Bit 1: Error in channel group 1 (I+0.4 ... I+0.7)
n
Bit 2: Error in channel group 2 (I+1.0 ... I+1.1)
n
Bit 3: reserved
n
Bit 4: Error in channel group 4 (counter 0)
n
Bit 5: Error in channel group 5 (counter 1)
n
Bit 6: reserved
n
Bit 7: reserved
Diagnostic record set 1
at counter function
VIPA System 300S
Deployment I/O periphery
Diagnostic and interrupt > Diagnostic interrupt
HB140 | CPU-SC | 312-5BE13 | GB | 15-50