The structure of a command file is shown in the following. The
corresponding diagnostics entry is put in parenthesizes.
CMD_START
Marks the start of the command sequence (0xE801)
LOAD_PROJECT proj.wld
Execute an overall reset and load "proj.wld" (0xE805)
WAIT1SECOND
Wait ca. 1s (0xE803)
WEBPAGE
Store web page as "webpage.htm" (0xE804)
DIAGBUF
Store diagnostics buffer of the CPU as "diagbuff.txt" (0xE80B)
CMD_END
Marks the end of the command sequence (0xE802)
... arbitrary text ...
Text after the command CMD_END is not evaluated.
CMD_START
Marks the start of the command sequence (0xE801)
LOAD_PROJECT proj2.wld
Execute an overall reset and load "proj2.wld" (0xE805)
WAIT1SECOND
Wait ca. 1s (0xE803)
WAIT1SECOND
Wait ca. 1s (0xE803)
SET_NETWORK172.16.129.210,255.255.224.0,172.16.129.210
IP parameter
(0xE80E)
WAIT1SECOND
Wait ca. 1s (0xE803)
WAIT1SECOND
Wait ca. 1s (0xE803)
WEBPAGE
Store web page as "webpage.htm" (0xE804)
DIAGBUF
Store diagnostics buffer of the CPU as "diagbuff.txt" (0xE80B)
CMD_END
Marks the end of the command sequence (0xE802)
... arbitrary text ...
Text after the command CMD_END is not evaluated.
Note!
The parameters IP address, subnet mask and gateway may be received
from the system administrator.
Enter the IP address if there is no gateway used.