Chapter 5 Deployment I/O periphery
Manual VIPA System 300S SPEED7
5-30
HB140E - CPU SC - RE_313-6CF03 - Rev. 07/45
Effect at pulse at comparison value with pulse duration not zero
8
7
6
5
4
3
2
1
0
Comparison value
Hysteresis
Output:
Hysteresis = 0
Hysteresis = 3
Counter value
1
2
3
4
5
6
7
1
Counter value
=
comparison value
→
pulse of the parameterized duration is put out, the
hysteresis is activated and the counting direction stored
2
Leaving the hysteresis range contrary to the stored counting direction
→
pulse of the
parameterized duration is put out, the hysteresis is de-activated
3
Counter value
=
comparison value
→
pulse of the parameterized duration is put out, the
hysteresis is activated and the counting direction stored
4
Leaving the hysteresis range without changing counting direction
→
hysteresis is de-activated
5
Counter value
=
comparison value
→
pulse of the parameterized duration is put out, the
hysteresis is activated and the counting direction stored
6
Counter value
=
comparison value and hysteresis active
→
no pulse
7
Leaving the hysteresis range contrary to the stored counting direction
→
pulse of the
parameterized duration is put out, the hysteresis is de-activated
With reaching the comparison condition the hysteresis gets active and a
pulse of the parameterized duration is put out. As long as the counter value
is within the hysteresis range, no other pulse is put out. With activating the
hysteresis the counting direction is stored in the CPU. If the counter value
leaves the hysteresis range contrary to the stored counting direction, a
pulse of the parameterized duration is put out. Leaving the hysteresis
range without direction change, no pulse is put out.