Chapter 4 Deployment CPU 313SC/DPM
HB140E - CPU SC - RE_313-6CF03 - Rev. 07/45
4-39
MMC-Cmd - Auto commands
A
command file at a MMC may be started a
utomatically when the MMC is
plugged and the CPU is in STOP. As soon as the MMC is stuck the
command file is once executed at CPU STOP up to the next PowerON.
The command file is a text file, which consists of a command sequence to
be stored as
vipa_cmd.mmc
in the root directory of the MMC.
The file has to be started by
CMD_START
as 1st command, followed by
the desired commands (no other text) und must be finished by CMD_END
as last command.
Text after the last command
CMD_END
e.g. comments is permissible,
because this is ignored. As soon as the command file is recognized and
executed each action is stored at the MMC in the log file logfile.txt. In
addition for each executed command a diagnostics entry may be found in
the diagnostics buffer.
In the following there is an overview of the commands. Please regard the
command sequence is to be started with
CMD_START
and ended with
CMD_END.
Command
Description
Diagnostics entry
CMD_START
In the first line
CMD_START
is to be located.
0xE801
There is a diagnostic entry if
CMD_START
is missing
0xE8FE
WAIT1SECOND
Waits ca. 1 second.
0xE803
WEBPAGE
The current web page of the CPU is stored at the MMC
as "webpage.htm".
0xE804
LOAD_PROJECT
The function "Overall reset and reload from MMC" is
executed. The wld file located after the command is
loaded else "s7prog.wld" is loaded.
0xE805
SAVE_PROJECT
The recent project (blocks and hardware configuration)
is stored as "s7prog.wld"
at the MMC.
If the file just exists it is renamed to "s7prog.old".
0xE806
FACTORY_RESET Executes "factory reset".
0xE807
DIAGBUF
The current diagnostics buffer of the CPU is stored as
"diagbuff.txt" at the MMC.
0xE80B
SET_NETWORK
IP parameters for Ethernet PG/OP channel may be set
by means of this command.
The IP parameters are to be given in the order IP
address, subnet mask and gateway in the format
xxx.xxx.xxx.xxx each separated by a comma.
Enter the IP address if there is no gateway used.
0xE80E
CMD_END
In the last line
CMD_END
is to be located.
0xE802
Overview
Commands