Manual VIPA System 300S SPEED7
Chapter 6 Deployment PtP communication
HB140E - CPU SC - RE_313-6CF03 - Rev. 07/45
6-9
Parameterization
The parameterization happens during runtime deploying the SFC 216
(SER_CFG). You have to store the parameters for STX/ETX, 3964R, USS
and Modbus in a DB.
Name
Declaration Type
Comment
Protocol
IN
BYTE
1=ASCII, 2=STX/ETX, 3=3964R
Parameter
IN
ANY
Pointer to protocol-parameters
Baudrate
IN
BYTE
Number of the baudrate
CharLen
IN
BYTE
0=5Bit, 1=6Bit, 2=7Bit, 3=8Bit
Parity
IN
BYTE
0=None, 1=Odd, 2=Even
StopBits
IN
BYTE
1=1Bit, 2=1.5Bit, 3=2Bit
FlowControl IN
BYTE
1
(fix)
RetVal
OUT
WORD
Return value (0 = OK)
All time settings for timeouts must be set as hexadecimal value. Find the
hex value by multiply the wanted time in seconds with the baudrate.
Example: Wanted time 8ms at a baudrate of 19200Baud
Calculation: 19200Bit/s x 0,008s
≈
154Bit
→
(9Ah)
Hex value is 9Ah.
Here you fix the protocol to be used. You may choose between:
1: ASCII
2: STX/ETX
3: 3964R
4: USS Master
5: Modbus RTU Master
6: Modbus ASCII Master
SFC 216
(SER_CFG)
Parameter
description
Protocol