Chapter 7 Deployment Profibus communication
HB140E - CPU SC - RE_313-6CF03 - Rev. 07/45
7-5
Deployment as Profibus DP slave
The deployment of the Profibus section as "intelligent" DP slave happens
exclusively at master systems that may be configured in the Siemens
SIMATIC manager. The following steps are required:
•
Start the Siemens SIMATIC manager and configure a CPU 313C-2DP
with the operating mode
DP slave
.
•
Connect to Profibus and configure the in-/output area for the slave
section.
•
Save and compile your project.
•
Configure another station as CPU 313C-2DP with operating mode
DP
master.
•
Connect to
Profibus
and configure the in-/output ranges for the master
section
•
Save and compile your project.
In the following these steps are more detailed.
•
Start the Siemens SIMATIC manager with a new project.
•
Insert a
SIMATIC 300 station
and name it as "...DP slave".
•
Open the hardware configurator and insert a profile rail from the
hardware catalog.
•
Place the following Siemens CPU at slot 2:
CPU 313C-2DP (6ES7 313-6CF03-0AB0 V2.0)
•
Add your modules according to the real hardware assembly.
•
Connect the CPU to
Profibus
, set a Profibus address >1 (preferably 3)
and switch the Profibus section via
operating mode
to "slave operation".
•
Via
Configuration
you define the in-/output address area of the slave
CPU that shall be assigned to the DP slave.
•
Save and compile your project.
Object properties
Operating mode: DP slave
Connect: Profibus
Profibus address: > 1
Configuration:
Input area
Output area
Slave section
Standard bus
Module
CPU 313C-2DP
DP
DI16/DO16
Count
...
I/O devices
Slot
1
2
X2
2.2
2.4
3
Fast introduction
Project
engineering of the
slave section