Chapter 4 Deployment CPU 313SC/DPM
Manual VIPA System 300S SPEED7
4-30
HB140E - CPU SC - RE_313-6CF03 - Rev. 07/45
At this point the CPU attempts to reload the parameters and the program
from the memory card.
→
The MCC-LED blinks.
When the reload has been completed the LED expires. The operating
mode of the CPU will be STOP or RUN, depending on the position of the
function selector.
Condition
The operating mode of the CPU must be STOP.
You may place the CPU in STOP mode by the menu command
PLC
>
Operating mode
.
Overall reset
You may request the overall reset by means of the menu command
PLC
>
Clean/Reset
.
In the dialog window you may place your CPU in STOP mode and start the
overall reset if this has not been done as yet.
The STOP-LED blinks during the overall reset procedure.
When the STOP-LED is on permanently the overall reset procedure has
been completed.
At this point the CPU attempts to reload the parameters and the program
from the memory card.
→
The MCC-LED blinks.
When the reload has been completed, the LED expires. The operating
mode of the CPU will be STOP or RUN, depending on the position of the
function selector.
The following approach deletes the internal RAM of the CPU completely
and sets it back to the delivery state.
Please regard that the MPI address is also set back to default 2!
•
Push down the reset lever for app. 30 seconds. The ST-LED blinks.
After a few seconds the LED turns to static light. Count the number of
static light phases because now the LED switches between static light
and blinking.
•
After the 6
th
static light you release the reset lever and push it down
again shortly. Now the green RUN-LED is on once. This means that the
RAM is totally deleted.
•
Turn the power supply off and on again.
More information may be found at the part "Factory reset" further below.
Automatic reload
Overall reset by
means of the
Siemens SIMATIC
Manager
Automatic reload
Set back to factory
setting