Specification
IP rating
IP 43 to EN 60529;
ensure through appropri-
ate design/installation
Sensor type
Viessmann NTC 10 kΩ at
25 °C
Permissible ambient temperature during
operation, storage and transport
-40 to +70 °C
Specification Vitotronic 200, type HO1A
Rated voltage
230 V~
Rated frequency
50 Hz
Rated current
6 A
Protection class
I
Permissible ambient
temperature
– during operation
0 to +40 °C
Installation in living spaces or boiler rooms
(standard ambient conditions)
– during storage and
transport
–20 to +65 °C
Electronic temperature
limiter setting (heating
mode)
82 °C (change not possible)
Setting range for the
DHW temperature
– Vitodens with pri-
mary store
10 to 63 °C
– Vitodens with DHW
cylinder with internal
indirect coil
10 to 68 °C
Heating curve setting
range
Slope
0.2 to 3.5
Level
-13 to 40 K
6.2 Vitotronic accessories
Information regarding room temperature hook-up (RS function) for remote control units
Due to the "inertia" of underfloor heating systems, the RS function
should not be applied to an underfloor heating circuit.
The RS function must only affect the heating circuit with mixer.
Information regarding the Vitotrol 200A and 300A
Vitotrol 200A and 300A may be combined in a single heating sys-
tem.
The Vitotrol 200A can regulate one heating circuit, the Vitotrol 300A
up to 3 heating circuits.
Vitotrol 200A
Part no. Z008 341
KM BUS subscriber
A Vitotrol 200A can be used for each heating circuit in a heating sys-
tem. Up to 2 remote controls may be connected to the control unit.
Functions:
■ Display of room temperature, outside temperature and the operating
condition.
■ Setting the standard room temperature (day temperature) and oper-
ating program via the standard display.
Note
The reduced room temperature (night temperature) is set at the con-
trol unit.
■ Party and economy mode can be enabled via keys
■ Only for heating circuit with mixer:
Room temperature sensor for room temperature hook-up
Note
For room temperature hook-up, the Vitotrol 200A must be installed
in the living space (lead room).
Installation location:
■ Weather-compensated mode:
Installation at any point in the building.
■ Room temperature hook-up:
Installation in the main living room on an internal wall opposite radi-
ators. Never install inside shelving units, in recesses, or immediately
by a door or heat source (e.g. direct sunlight, fireplace, TV set, etc.).
The integral room temperature sensor captures the actual room
temperature and effects any necessary correction of the flow tem-
perature as well as a rapid heat-up at the start of the heating oper-
ation (if suitably encoded).