Sizing the oil line
Suction head H in m max. cable length in m when the suction
line has the following diameter:
6x1 mm
8x1 mm
+4.0
100
100
+3.5
95
100
+3.0
89
100
+2.5
83
100
+2.0
77
100
+1.5
71
100
+1.0
64
100
+0.5
58
100
0.0
52
100
-0.5
46
100
-1.0
40
100
-1.5
33
100
-2.0
27
100
-2.5
21
100
-3.0
15
75
-3.5
9
44
-4.0
—
12
A total pressure drop of 0.35 bar is assumed, based on fuel oil EL with
6.0 cSt (DIN 51603-1) including 1 shut-off valve, 1 foot valve and 1 fuel
oil filter.