Vitocom 100, type GSM
■ Without SIM card
Part no. Z004594
■ With contract SIM card for the operation of the Vitocom 100 via
mobile phone
Part no. Z004615
Note
For further information regarding the conditions of contract, see the
Viessmann pricelist.
Functions:
■ Remote switching via GSM mobile phone networks
■ Remote scanning via GSM mobile phone networks
■ Remote monitoring via SMS to 1 or 2 mobile phones
■ Remote monitoring of additional systems via digital input (230 V)
Configuration:
Mobile phones via SMS
Standard delivery:
■ Vitocom 100 (subject to order with or without SIM card)
■ Power supply cable with Euro plug (2.0 m long)
■ GSM aerial (3.0 m long), magnetic foot and adhesive pad
■ KM BUS cable (3.0 m long)
On-site requirements:
Good reception for GSM communication of the selected mobile phone
operator.
Total length of all KM BUS subscriber cables up to 50 m.
72
130
50
Specification
Rated voltage
230 V ~
Rated frequency
50 Hz
Rated current
15 mA
Power consumption
4 W
Protection class
II
Protection
IP 41 to EN 60529; safeguard
through appropriate design
and installation
Function
Type 1B to EN 60 730-1
Permissible ambient temperature
– during operation
0 to +55 °C
Installation in living spaces or
boiler rooms (standard ambi-
ent conditions)
– during storage and transport
-20 to +85 °C
On-site connection
Fault input DE 1
230 V~
Extension kit for one heating circuit with mixer with integral mixer motor
Part no. 7301 063
KM BUS subscriber
Components:
■ Mixer PCB with mixer motor for Viessmann mixer DN 20 to 50 and
R ½ to 1¼
■ Flow temperature sensor (contact temperature sensor), lead length
2.2 m, fully wired, for specification see below
■ Connecting plug for the heating circuit pump
■ Power cable (3.0 m long)
■ BUS cable (3.0 m long)
The mixer motor is mounted directly onto the Viessmann mixer DN 20
to 50 and R ½ to 1¼.
Mixer PCB with mixer motor
160
180
130
Specification
Rated voltage
230 V~
Rated frequency
50 Hz
Rated current
2 A
Power consumption
5.5 W
IP rating
IP 32D to EN 60529
ensure through appropriate
design/installation
Protection class
I
Permissible ambient temperature
– during operation
0 to +40 °C
– during storage and transport
–20 to +65 °C
Rated breaking capacity of the relay
output for heating circuit pump
sÖ
2(1) A 230 V~
Torque
3 Nm
Runtime for 90 °
∢
120 s
Flow temperature sensor (contact sensor)
42
66
60
Secured with a tie.
Control unit
(cont.)
62
VIESMANN
VITOLADENS 300-W
/
VITOLADENS 333-F
6
5822 425 GB