Troubleshooting
56
Diagnostics
(continued)
Fault codes
(continued)
Fault code on display
System behavior
*1
Cause
Corrective action
40
Mixing valve closes
Heating circuit with mixing
valve supply temperature
sensor shorted out
Check the supply
temperature sensor
(see page 60).
48
Mixing valve closes
Heating circuit with mixing
valve supply temperature
sensor cable broken
Check the supply
temperature sensor
(see page 60).
50
No DHW heating
Tank temperature
sensor shorted out
Check the sensor
(see page 60).
58
No DHW heating
Tank temperature sensor
cable broken
Check the sensor
(see page 60).
92
Control mode
Collector temperature sensor
shorted out; connects to the
Vitosolic at S1
Check the sensor at the
Vitosolic solar control.
93
Control mode
Collector temperature sensor
shorted out; connects to the
Vitosolic at S3
Check the sensor at the
Vitosolic solar control.
94
Control mode
Collector temperature sensor
shorted out; connects to the
Vitosolic at S2
Check the sensor at the
Vitosolic solar control.
9A
Control mode
Collector temperature sensor
cable broken; connects to the
Vitosolic at S1
Check the sensor at the
Vitosolic solar control.
9b
Control mode
Tank temperature sensor
cable broken; connects to the
Vitosolic at S3
Check the sensor at the
Vitosolic solar control.
9C
Control mode
Tank temperature sensor
cable broken; connects to the
Vitosolic at S2
Check the sensor at the
Vitosolic solar control.
9F
Control mode
Solar control unit fault;
displayed if a fault without
fault code occurs at the solar
control unit
Check the solar control unit
(see solar control service
instructions).
A7
Control mode (stays in
factory default setting)
Faulty programming unit
Replace the programming
unit.
b0
Burner blocked
Flue gas temperature sensor
shorted out
Check flue gas temperature
sensor (see page 61).
b1
Control mode (stays in
factory default setting)
Communication fault;
programming unit (internal)
Check connections and
replace programming unit if
required.
b4
Regulates as if the outdoor
temperature was 0°C
Internal fault
Replace the control unit.
b5
Control mode
(factory default setting)
Internal fault
Replace the control unit.
b7
Burner blocked
Boiler coding card missing,
faulty or incorrect boiler
coding card
Plug in boiler coding card or
replace if faulty.
b8
Burner blocked
Flue gas temperature sensor
cable broken
Check flue gas temperature
sensor (see page 61).