Control Technology
35
Outdoor Reset Programming Unit
(continued)
Connecting the boiler control to a LON system
(continued)
Performing participant check
Conditions:
A
Consecutive number in the
participant list
B
Participant number
H
The control unit must be
programmed
as fault manager (code ”79:1”)
H
The LON participant number must
be programmed in all control units
(see table on previous page)
H
The LON participant list in the fault
manager must be up-to-date (see
table on page 33)
1.
Press “
w
“ + “
” simultaneously
for approx. 2 sec. Participant check
is initiated.
2.
Press “
⊕
/
“ for required
participant.
3.
Press
“
”
. Check is
enabled.”Check” flashes until its
completion. The display and all key
illuminations for the selected
participant flash for approx. 60 sec.
4.
”
Check OK
” is displayed during
communication between both
devices.
or
”
Check not OK
” is displayed if
there is no communication
between both devices. Check the
LON connection.
5.
Repeat steps 2 and 3 to check
other participants.
6.
Press
“
w
“ +
“
”
simultaneously
for approx. 1 sec. The participant
check is completed.
Instructing the system user
The system installer must hand the operating instructions to the system user
and instruct him/her in the operation of the system.