Coding
41
Coding Level 2
(continued)
Overview of coding addresses
Coding (factory default setting)
Possible change
System design
00 :1
System type 1, 2:
1 heating circuit without mixing
valve, without DHW heating
00 :2
System type 1, 2:
1 heating circuit without a mixing valve,
with DHW heating
00 :3
System type 3, 6, 8:
1 heating circuit with mixing valve, without DHW heating
00 :4
System type 3, 6, 8:
1 heating circuit with mixing valve, with DHW heating
00 :5
System type 4, 5, 7:
1 heating circuit without mixing valve and 1 heating circuit
with mixing valve, without DHW heating
00 :6
System type 4, 5, 7:
1 heating circuit without mixing valve; 1 htg. circuit with
mixing valve, with DHW htg.
Boiler/Burner
06:...
Maximum limit of the boiler
water temperature, defaulted by
the boiler coding card
06:20
to
06:127
Maximum limit of the boiler water temperature within the
ranges defaulted by the boiler coding card
07:1
Boiler number in multiboiler
system (only with Vitocontrol-S
and Vitotronic 100 control).
07:2
to
07:4
Boiler number 2 to 4 in multiboiler system (only with
Vitocontrol-S and Vitotronic 100 control).
11:
≠
9
No access to the coding
addresses for the parameters
of the combustion controller
11:9
Access open to the coding addresses for the
parameters of the combustion controller
12:0
Special function OFF
Always reset to 12:0 if
“possible change”
used.
12:1
12:2
Special function ON:
During calibration, the control automatically sets the boiler
water temperature to max.
If automatic calibration is initiated, the boiler will not start
unless the temperature falls below 42°C/108°F (see fault
Eb before adjusting).
21:0
No maintenance interval
(operating hours)selected
21:1
to
21:100
The number of hours run before the burner should be
serviced is adjustable from 0 to 100
(each increment = 100 hr.).
23:0
No time interval for burner
service selected
23:1
to
23:24
Interval adjustable from 1 to 24 months
24:0
The service display is reset
24:1
Service display (value displayed automatically)
28:0
No burner interval ignition
28:1
to
28:24
Time interval adjustable from 1 to 24 h. The burner is
force-started once for 30 sec. within selected time interval.
(only adjustable if coding address 82:_ has been set to 1).
2E:0
KM-BUS connection of power/
pump module not recognized
2E:1
KM-BUS connection of power/pump module automatically
recognized.
2F:0
Air bleed program/fill program
disabled
2F:1
Air bleed program enabled
2F:0
Air bleed program/fill program
disabled
2F:2
Fill program enabled
32:0
*1
Influence of the signal ”External
blocking” on circulation pumps:
All pumps in control function
32:1
to
32:15
Influence of the signal ”External blocking” on
circulation pumps: see the following table
*1
Generally, the burner will be blocked when signal ”External blocking” is enabled.
5
4
4
3
2
0
7
v
1
.5