Control Technology
33
Outdoor Reset Programming Unit
(continued)
Connecting the boiler control to a LON system
Vitocom LON Communication Module (accessory) must be connected.
Installation Instructions
LON Communication Module
Note:
Data transfer via LON can take several minutes.
Single-boiler system with Vitotronic 200-H, HK1M and Vitotronic 200-H, HK1S
mixing valve controls and Vitocom LON communication module
Set up the LON participant numbers and other functions via coding level 2
(see table below).
Note:
In the same LON system, a number
cannot
be allocated twice.
Only one Vitotronic
may be programmed as fault manager.
Boiler Control
Unit
Vitotronic 200-H
(e.g. HK1M mixing
valve control)
Vitotronic 200-H
(e.g. HK1S
*1
multiple mixing
valve control)
Vitocom
*1
LON
communication
module
LON
LON
LON
Participant no. 1
Code ”77:1”
Participant no. 10
Code ”77:10”
Participant no. 11
Code ”77:11”
Participant no. 99
Control unit is
fault manager
Code ”79:1”
Control unit is not
fault manager
Code ”79:0”
Control unit is not
fault manager
Code ”79:0”
Device is fault
manager
Control unit
transmits the
time
Code ”7b:1”
Control unit
receives the time
Set code ”81:3”
Control unit
receives the time
Set code ”81:3”
Device receives
the time
Control unit
transmits outdoor
temperature
Set code ”97:2”
Control unit
receives outdoor
temperature
Set code ”97:1”
Control unit
receives outdoor
temperature
Set code ”97:1”
--
LON participant
fault monitoring
Code ”9C:20”
LON participant
fault monitoring
Code ”9C:20”
LON participant
fault monitoring
Code ”9C:20”
--
*1
Refer to separate Installation Instructions of accessories.
5
4
4
3
2
0
7
v
1
.5