Initial Start-up and Service
15
Steps
(continued)
10.Measure static pressure and running pressure
I
nitial start-up
S
ervice
1.
To measure static and/or running
pressure remove boiler enclosure
panel as indicated page 9 in these
instructions.
2.
Close gas shutoff valve (field
supplied).
3.
Loosen screw
A
at inlet gas
pressure port on one of the two gas
combination valves,
do not remove
completely.
Connect manometer.
4.
Open the gas shutoff valve.
5.
Measure static pressure. Value must
be 14 “w.c. max. for NG and LPG.
6.
Enter measured value into
Maintenance Record on page 73 in
this manuals.
7.
Start up boiler, using the ON/OFF
switch “
8
” on the boiler control.
A CO measurement (see page 24) must
be taken before and after working on
gas appliances to eliminate risks to
health and to guarantee the
satisfactory condition of the system.
The burner is automatically ignited and
starts operation after a safety time has
elapsed.
During initial start-up, the unit may
indicate a fault because of air in the gas
supply pipe (especially for liquid propane
gas).
After approx. 5 seconds, press the reset
”
E
E
E
E
” button to reset the burner. The
ignition procedure is repeated. This
boiler employs a direct spark ignition
system.
8.
Measure the running pressure; value
must be:
Use suitable measuring instruments
calibrated with a minimum resolution
of 0.04 “w.c. for measuring the
running pressure.
Running supply pressure with
Corrective action
Natural gas
Liquid propane gas
under 4 ”w.c.
under 10 ”w.c.
Do not attempt adjustment. Call local gas utility
to increase pressure.
4 to 14 “w.c.
10 to 14 ”w.c.
Start up boiler.
over 14 ”w.c.
over 14 ”w.c.
Do not attempt adjustment. Call local gas utility
to decrease pressure. Boiler valve must not be
exposed to pressure over 14 ”w.c.
9.
Enter gas type into Maintenance
Record on page 73 in this manual.
10.
Switch off the ON/OFF switch “
8
”
on the boiler control, close the gas
shut-off valve, remove the
manometer and re-tighten the
screw
A
at inlet gas pressure
port.
5
4
4
3
2
0
7
v
1
.5
Fig. 7
Measuring gas supply pressure
at inlet gas pressure port
inlet
outlet
A
A
IMPORTANT
IMPORTANT
Ensure that there is no open flame in
the room.
WARNING
Never purge a gas line into a
combustion chamber. Never use
matches, candles, flame, or other
sources of ignition for purpose of
checking leakage. Use a
soap-and-water solution to check for
leakage. A failure to follow this
warning could result in fire,
explosion, personal injury, or death.
WARNING