DHW cylinder selection tables
DHW cylinders with "-W" in the product name are supplied with a
white finish. Appliances with "-B" or "-V" in the product name are
supplied in Vitosilver (marked in grey in the table).
Vitodens 200-W gas system boilers, cylinder allocation
Practical cylinder allocation (cylinder capacity in litres)
Rated heating output range [kW]
up to 19.0
25.0
32.0
Vitocell 100-W (type CUGA, CUGA-A) below the boiler
120
150
120
150
120
150
Vitocell 100-W (type CVA, CVAA, CVAA-A) adjacent to
the boiler
160
200
300
160
200
300
160
200
300
Vitocell 100-V (type CVA) adjacent to the boiler
—
—
500
Vitocell 200-W (type EVIA-A) adjacent to the boiler
160
200
160
200
160
200
Vitocell 300-V (type EVIA-A) adjacent to the boiler
—
300
500
300
500
Vitocell 100-W (type CVB, CVBB) adjacent to the boil-
er, dual mode
300
400
300
400
300
400
Vitocell 100-W (type CVUB) adjacent to the boiler, dual
mode
300
300
300
Vitocell 100-W (type CVUC-A) adjacent to the boiler,
dual mode (for Vitodens 200-W only)
300
300
300
Vitocell 100-B (type CVB) adjacent to the boiler, dual
mode
—
500
500
Vitocell 300-B (type EVBA-A) adjacent to the boiler,
dual mode
300
300
500
300
500
Vitocell 340-M (type SVKC) heating water buffer cylin-
der with DHW heating
708/30
708/30
708/30
Vitocell 360-M (type SVSB) heating water buffer cylin-
der with DHW heating
708/30
708/30
708/30
8.3 Connections on the water side
Connection on the DHW side
Vitodens 200-W gas condensing combi boiler
For the DHW connection, connection sets for surface or flush mount-
ing are available as accessories. The instantaneous water heater
provides direct DHW heating.
If used in conjunction with galvanised pipes, note that the instanta-
neous water heater is designed as a stainless steel plate heat
exchanger with copper solder joints (observe the flow rule).
In existing installations (modernisation projects), the risk of electro-
lytic corrosion is low, since a protective layer will have formed on the
inside of the pipes.
If DHW is to be drawn simultaneously from several points, we rec-
ommend the installation of a separate DHW cylinder in conjunction
with the gas system boiler (see "Decision making aids regarding
DHW heating").
With water hardness of 20 °dH and higher, we recommend the use
of a water treatment system in the cold water line when heating
DHW.
Design information
(cont.)
VITODENS
VIESMANN
127