Pressure drop on the DHW side
DHW flow rate
in l/h
mbar
1000
5
10
20
50
100
200
500
1000
2000
3000
5000
7000
A
B
Pressure drop
kPa 0.5
1
2
5
10
20
50
100
A
160 and 200 l
B
300 l
DHW output data at rated heating output
Rated heating output for DHW heating
kW
17.3
22.7
29.1
Continuous DHW output
for DHW heating from 10 to 45 °C and an average boiler
water temperature of 78 °C
Cylinder capacity 160 and 200 l
kW
17.3
22.7
26
l/h
425
555
638
Cylinder capacity 300 l
kW
17.3
22.7
29.1
l/h
425
555
715
Performance factor N
L
to DIN 4708
Cylinder capacity 160 l
2.1
2.2
2.2
Cylinder capacity 200 l
3.1
3.2
3.2
Cylinder capacity 300 l
7.5
8.0
8.0
Peak output
over 10 minutes
Cylinder capacity 160 l
l/10 min
192
199
199
Cylinder capacity 200 l
l/10 min
233
236
236
Cylinder capacity 300 l
l/10 min
360
368
368
Delivered condition
DHW cylinder made from steel with Ceraprotect enamel coating.
■ Integral welded sensor well for cylinder temperature sensor or
temperature controller
■ Threaded adjustable feet
■ Protective magnesium anode
■ Fitted thermal insulation
Separate DHW cylinders for Vitodens 200-W