1.2 Specification
Gas condensing system boiler
Gas boiler, type B and C, category II
2N3P
Type
B2HE
Rated heating output range (details to EN 15502)
T
F
/T
R
= 50/30 °C
Natural gas
kW
1.9 - 11.0
1.9 - 19.0
1.9 - 25.0
1.9 - 32.0
LPG
kW
2.5 - 11.0
2.5 - 19.0
2.5 - 25.0
2.5 - 32.0
T
F
/T
R
= 80/60 °C
Natural gas
kW
1.7 - 10.1
1.7 - 17.4
1.7 - 22.9
1.7 - 29.3
LPG
kW
2.2 - 10.1
2.2 - 17.4
2.2 - 22.9
2.2 - 29.3
Rated heating output for DHW heating
Natural gas
kW
1.7 - 17.4
1.7 - 17.4
1.7 - 22.9
1.7 - 29.3
LPG
kW
2.2 - 17.4
2.2 - 17.4
2.2 - 22.9
2.2 - 29.3
Rated heat input
Natural gas
kW
1.8 - 17.8
1.8 - 17.8
1.8 - 23.4
1.8 - 29.9
LPG
kW
2.3 - 17.8
2.3 - 17.8
2.3 - 23.4
2.3 - 29.9
Product ID
CE-0085CT0017
IP rating
to EN 60529
IP X4
Gas supply pressure
Natural gas
mbar
kPa
20
2
20
2
20
2
20
2
LPG
mbar
kPa
50
5
50
5
50
5
50
5
Max. permiss. gas supply pressure
*1
Natural gas
mbar
kPa
25.0
2.5
25.0
2.5
25.0
2.5
25.0
2.5
LPG
mbar
kPa
57.5
5.75
57.5
5.75
57.5
5.75
57.5
5.75
Sound power level
(to EN ISO 15036-1)
At partial load
dB(A)
27
27
27
27
At rated heating output (DHW heating)
dB(A)
41
41
42
47
Power consumption
(in the delivered condition)
W
37
47
68
92
Weight
– Excl. heating water and packaging
kg
33.0
33.0
33.0
33.0
– Incl. heating water
kg
38.6
38.6
38.6
38.6
Water capacity
(excl. diaphragm expansion vessel)
l
3.0
3.0
3.0
3.0
Max. flow temperature
°C
82
82
82
82
Max. flow rate
(Limit for the use of hydraulic separation)
l/h
See residual head graph
Nominal circulating water volume
At T
F
/T
R
= 80/60 °C
l/h
473
818
1076
1374
Diaphragm expansion vessel
Capacity
l
10
10
10
10
Pre-charge pressure
bar
kPa
0.75
75
0.75
75
0.75
75
0.75
75
Permiss. operating pressure
bar
MPa
3
0.3
3
0.3
3
0.3
3
0.3
Dimensions
Length
mm
360
360
360
360
Width
mm
450
450
450
450
Height
mm
700
700
700
700
Gas connection
R
¾
¾
¾
¾
Supply values
Relative to the max. load and 1013 mbar/15 °C
With gas
Natural gas E
m
3
/h
1.88
1.88
2.48
3.16
Natural gas LL
m
3
/h
2.19
2.19
2.88
3.68
LPG
kg/h
1.38
1.38
1.82
2.32
*1
If the gas supply pressure is higher than the maximum permissible value, install a separate gas pressure governor upstream of the sys-
tem.