56
Remote control for heating/cooling circuit or Vitocomfort 200
Parameter
Setting
"Heating circuit 1"
/
"Heating circuit 2"
/
"Heating circuit 3"
Ó
"Remote control 2003"
or
"Remote control 3003"
or
"Remote control 4003"
"1"
Note
To assign a heating circuit, set the
code at the remote control:
See "Vitotrol" installation instructions.
Vitocom 100, type GSM2
Parameter
Setting
"System definition"
Ó
"Vitocom 100 7017"
"1"
External extension
Parameter
Setting
"System definition"
Ó
"External extension 7010"
"1"
EA1 extension
"2"
AM1 extension
"3"
EA1 and AM1 extensions
Note
For parameters for external functions,
see the following table.
Heat pump stage 2
Parameter
Setting
"Compressor 2"
Ó
"Enable compressor 5100"
"1"
"Output compressor stage 5130"
Value corresponding to the rated heat-
ing output of heat pump stage 2: See
type plate.
Parameters for external functions
External demand
Parameter
Setting
"Internal hydraulics"
Ó
if necessary
"Flow temperature external demand 730C"
Set flow temperature for external de-
mand
External starting of the compressor; mixer in control mode or OPEN
Parameter
Setting
"System definition"
Ó
"Effect of external demand on heat pump/heating circuits
7014"
"0"
to
"7"
(Observe parameter
"Flow tempera-
ture external demand 730C"
)
Commissioning, inspection, maintenance
Commissioning the system
(cont.)
5855006