12
!
Please note
Impacts, compression and tensile loads can
cause damage to the outside panels of the
appliance.
Never
put weight on the top, front or side panels
of the appliance.
!
Please note
Tilting the compressor at a steep angle inside
the heat pump can result in appliance damage.
Max. tilting angle: 45° for a very short time
Installation room requirements
!
Please note
Unfavourable ambient conditions can lead to
malfunctions and appliance damage.
The installation room must be dry and free from
the risk of frost:
■
Ensure ambient temperatures between 0 and
35 °C.
■
Max. 70 % relative humidity (corresponds to
an absolute humidity of approx. 25 g water
vapour/kg dry air)
Danger
Dust, gases and vapours can be damaging to
health and trigger explosions.
Avoid dust, gases and vapours in the installation
room.
!
Please note
Overloading the floor can result in damage to
the building structure.
Observe the permissible floor load. Take the
total weight of the appliance into account.
Total weight
Type
Weight in kg
BW
351.B20
270
351.B27
285
351.B33
310
351.B42
315
Type
Weight in kg
BWS
351.B20
265
351.B27
280
351.B33
305
351.B42
310
To prevent the transmission of structure-borne noise,
never site the appliance above ceilings with wooden
joists, e.g. in the attic.
Minimum room volume (to EN 378)
Type
Refrigerant
charge in kg
Minimum
room volume
in m
3
■
BW
■
BWS
351.B20
5.3
12.1
351.B27
7.0
15.9
351.B33
8.6
19.6
351.B42
8.7
19.8
Minimum clearances for 1-stage (type BW 351.B)
≥
400
≥
400
≥
1500
A
Fig. 3
A
Clearance subject to on-site installation and site
conditions
Note
■
Observe clearances for installation and mainte-
nance.
■
Additional strain relief clamps are required for the
power cables if the clearance behind the heat pump
is more than 80 mm.
Preparing for installation
Siting and transport requirements
(cont.)
5855006
Installation