Heating circuit 3
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
Service
"Standard room temperature"
4000
200 (
≙
20 °C)
"Reduced room temperature"
4001
160 (
≙
16 °C)
"Remote control"
4003
0
Room temperature control
4005
0
"Heating curve level"
4006
0 (
≙
0 K)
"Heating curve slope"
4007
6 (
≙
0.6)
"Influence room temperature hook-up"
400 A
10
"Room temperature hook-up"
400 B
0
"Max. flow temperature heating circuit"
400E
400 (
≙
40 °C)
Runtime mixer heating circ
4015
Do not adjust.
"Room temperature in party mode"
4022
200 (
≙
20 °C)
Cooling
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
Service
"Cooling function"
7100
0
"Cooling circuit"
7101
1
"Set room temperature separate cooling
circuit"
7102
200 (
≙
20 °C)
"Min. flow temperature cooling"
7103
200 (
≙
20 °C)
"Influence room temperature hook-up
cooling circuit"
7104
0
Room temperature control cooling circuit
7105
1
"Ranking room temp sensor separate
cooling circuit"
7106
0
Hysteresis room temp cooling circuit
7107
10 (
≙
1 K)
Enable flow temperature sensor cooling cir-
cuit
7109
1
"Cooling curve level"
7110
0 (
≙
0 K)
"Cooling curve slope"
7111
12 (
≙
1.2)
"Remote control cooling circ"
7116
0
Dew point monitor
7117
1
"Enable active cooling"
71FE
0
Ventilation: Vitovent 200-C and Vitovent 300-F
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
service
Vitovent enable
7D00
0
Enable preheater bank electric
7D01
0
Enable reheater bank hydraulic
7D02
0
Enable humidity sensor
7D05
0
Enable CO2 sensor
7D06
0
Set room temperature
7D08
200 (
≙
20 °C)
Flow rate reduced ventilation
7D0A
■
Vitovent 200-C:
75 m
3
/h
■
Vitovent 300-F:
120 m
3
/h
Commissioning/service reports
Control parameter report
(cont.)
5855006