87
Cooling function
Parameters for cooling function
Setting
"Cooling"
Ó
"Cooling 7100"
"3"
"Cooling"
Ó
"Cooling circuit 7101"
■
"1"
(heating circuit A1/HC1)
■
"2"
(heating circuit M2/HC2)
■
"4"
(separate cooling circuit
SKK)
Instantaneous heating water heater
Parameters for
instantaneous heating water heater
Setting
"Electr booster heater"
Ó
"Enable instantaneous heating water heater
7900"
"1"
"Electr booster heater"
, if applicable
Ó
"Enable instant. heating water heater for cen-
tral heating 7902"
"1"
"Electr booster heater"
Ó
"Output for instant. heating water heater at
power-OFF 790A"
■
"1"
for 3 kW
■
"2"
for 6 kW
■
"3"
for 9 kW
"DHW"
, if applicable
Ó
"Enable electric heaters for DHW heating
6015"
"1"
Checking the system function (e.g. actuators, temperatures,
poss. heat meter)
!
Please note
If the heat pump is exposed to
temperatures below –15 °C, e.g.
during storage or transport, the
high limit safety cut-out of the
instantaneous heating water
heater may respond.
Heat up the high limit safety cut-
out to above 20 °C and press
reset button
A
of the high limit
safety cut-out.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5600 950 GB