50
A
Expansion PCB on main PCB (con-
nect nothing on site)
B
Main PCB (see page 50)
F3 Fuse 6.3 A (slow)
C
Controller and sensor PCB (see
page 55)
D
AVI PCB (see page 56)
F101 Fuse 1.0 A (slow)
E
Luster terminals (see page 53)
F1 Fuse 6.3 A (slow)
F
Control module and power supply
for instantaneous heating water
heater
Main PCB (230 V~ function components)
Information regarding the connection
values
■ The specified output is the recommen-
ded connected load.
■ The total output of all components con-
nected directly to the heat pump con-
trol unit must not exceed 1000 W (e.g.
pumps, valves, message facilities,
contactors).
If the total output is < 1000 W, the indi-
vidual rating of a component (e.g.
pump, valve, message facility, contac-
tor) can be greater than specified.
However, the breaking capacity of the
corresponding relay must not be
exceeded.
■ The specified current indicates the
max. switching current of the switching
contact (observe the total current of
5 A).
Set the required parameters during com-
missioning; see from page 81.
Installation sequence
Electrical connection
(cont.)
5600 950 GB