System layout 2
The controller calculates the temperature difference bet-
ween collector sensor S1 and tank sensor S2. If the diffe-
rence is larger than or identical to the adjusted switch-on
temperature difference (DT O), the solar pump will be
operated by relay 1, and the tank will be loaded until the
switch-off temperature difference (DT F) or the maximum
tank temperature (S MX) is reached.
Arr 2
Tank 1
Tank 2
Display Channels
Channel
Description
Terminal
Page
INIT
x*
ODB initialization active
-
37
FLL
x*
ODB filling time active
-
37
STAB
x*
ODB stabilization in progress
-
37
COL
x
Temperature collector
S1
37
TST1
x
Temperature tank 1 bottom
S2
37
TSTT
x
Temperature tank 1 at the top
S3
37
TST2
x
Temperature tank 2 bottom
S4
37
n1 %
x
Pump speed R1
R1
38
n2 %
x
Pump speed R2
R2
38
h P1
x
Operating hours R1
R1
38
h P2
x
Operating hours R2
R2
38
TIME
x
Time
-
34
Heat exchange from tank 1 to tank 2 will be operated by
relay 2, if the temperature difference between sensors S3
and S4 is larger than or identical to the adjusted switch-on
temperature difference (DT3O), until the adjusted minimum
(MN3O) and maximum (MX3O) temperature thresholds of
the respective tanks are reached.