The controller calculates the temperature difference bet-
ween collector sensor S1 and tank sensor S2. If the diffe-
rence is larger than or identical to the adjusted switch-on
temperature difference (DT O), the solar pump will be
operated by relay 1, and the tank will be loaded until the
switch-off temperature difference (DT F) or the maximum
tank temperature (S MX) is reached.
If the maximum collector temperature (CMX) is reached, the
solar pump will be operated by relay 1 and the 3-way-valve
S1
S2
S4 / TR
R1
S3
R2
Display Channels
Channel
Description
Terminal
Page
COL
x
Temperature collector
S1
37
TST
x
Temperature tank
S2
37
S3
x
Temperature sensor 3
S3
37
S4
x
Temperature sensor 4
S4
37
TR
x*
Temperature return sensor
S4
37
n %
x
Pump speed relay
R1
30
h P1
x
Operating hours R1
R1
38
h P2
x
Operating hours R2
R2
38
kWh
x*
Heat quantity kWh
-
38
MWh
x*
Heat quantity MWh
-
38
TIME
x
Time
-
34
will be operated by relay 2 in order to direct the surplus
energy to a heat dump. For security purpose this will be
carried out only if the tank temperature is below the non-
adjustable emergency shutdown of 200 °F.
Sensors S3 and S4 can optionally be connected for mea-
surement purposes.
If energy metering (OHQM) is activated, sensor S4 has to
be connected as return sensor.