R2
System layout 8
The controller calculates the temperature difference bet-
ween collector sensor S1 and tank sensor S2. If the diffe-
rence is larger than or identical to the adjusted switch-on
temperature difference (DT O), the solar pump will be
operated by relay 1, and the tank will be loaded until the
switch-off temperature difference (DT F) or the maximum
tank temperature (S MX) is reached.
Arr 8
Display Channels
Channel
Description
Terminal
Page
INIT
x*
ODB initialization active
-
37
FLL
x*
ODB filling time active
-
37
STAB
x*
ODB stabilization in progress
-
37
COL
x
Temperature collector
S1
37
TSTB
x
Temperature tank 1 bottom
S2
37
TSTT
x
Temperature tank 1 at the top
S3
37
TSFB
x
Temperature solid fuel boiler
S4
37
n1 %
x
Pump speed R1
R1
38
n2 %
x
Pump speed R2
R2
38
h P1
x
Operating hours R1
R1
38
h P2
x
Operating hours R2
R2
38
TIME
x
Time
-
34
A solid fuel boiler will be operated by relay 2, if the tempera-
ture difference between sensors S4 and S3 is larger than or
identical to the adjusted switch-on temperature difference
(DT3O), until the adjusted minimum (MN3O) and maximum
(MX3O) temperature thresholds of the fuel boiler and the
tank are reached.