44
2-stage (type BW 301.B + BWS 301.B)
X3.7
X3.6
C
B
A
H
D
F
E
5
4
3
3
4
4
3
3/N
3/N
≈
4
G
kWh
kWh
K
4
Fig. 34
Shown without fuses and RCDs
A
Heat pump control unit (connection on cross con-
nect PCB)
B
Instantaneous heating water heater (if installed)
C
Compressor, heat pump stage 1 (type BW 301.B)
D
Premium tariff meter
E
Ripple control receiver (contact open: Power-OFF
enabled)
F
Backup fuse, ripple control receiver
G
Feed: TNC system
H
Economy tariff meter
K
Compressor, heat pump stage 2 (type BWS 301.B)
Power supply with power-OFF: With on-site load disconnect
The power-OFF signal is connected to the on-site con-
tactor of the economy tariff power supply and to the
heat pump control unit. When power-OFF is enabled,
the compressor
and
the instantaneous heating water
heater (if installed) are "forced" off; in the 2-stage ver-
sion (type BW 301.B + BWS 301.B), this applies to
both
compressors
and
the instantaneous heating
water heater.
Note
Observe the technical connection conditions of the rel-
evant power supply utility.
Installation sequence
Power supply
(cont.)
5516461
Installation
Summary of Contents for BW 301.B06
Page 69: ...69 Fig 49 Maintenance Opening the casing door 5516461 Maintenance...
Page 76: ...76 Maintenance Condensation and moisture in the heat pump cont 5516461 Maintenance...
Page 79: ...79 Parts lists type BWC 301 B Parts not shown type BWC 301 B cont 5516461 Components...
Page 88: ...88 Parts lists type BWC 301 B Hydraulics type BWC 301 B cont 5516461 Components...
Page 91: ...91 Parts lists type BW 301 B Parts not shown type BW 301 B cont 5516461 Components...
Page 100: ...100 Parts lists type BW 301 B Hydraulics type BW 301 B cont 5516461 Components...
Page 103: ...103 Parts lists type BWS 301 B Parts not shown type BWS 301 B cont 5516461 Components...