28
Overview of the electrical connections of the heat pump control unit (type BW/BWC 301.B)
X2
X3
F1
X1
X31
X25
X24
F0
F4
F27
F8
F6
F13
F7
F11
F12
F14
F16
F20
193B
193C
F3
193A
F26
J4
J3
Fig. 22
A
Cross connect PCB: See page 36.
F1 Fuse 6.3 A (slow)
B
Expansion PCB on main PCB: See page 32.
C
Main PCB: See next chapter.
F3 Fuse 6.3 A (slow)
D
Controller and sensor PCB: See page 38.
Main PCB (230 V~ components)
Information regarding the connection values
■
The specified output is the recommended connected
load.
■
The total output of all components connected directly
to the heat pump control unit (e.g. pumps, valves,
message facilities, contactors) must not exceed
1000 W.
If the total output is < 1000 W, the individual rating of
a component (e.g. pump, valve, message facility,
contactor) can be greater than specified. However,
the breaking capacity of the corresponding relay
must not be exceeded.
■
The stated current indicates the max. switching cur-
rent of the switching contact (observe the total cur-
rent of 5 A).
■
Controls for external heat source and central fault
messages are unsuitable for safety LV.
Set the required parameters during commissioning:
See page 55 onwards.
Installation sequence
Electrical connection
(cont.)
5516461
Installation
Summary of Contents for BW 301.B06
Page 69: ...69 Fig 49 Maintenance Opening the casing door 5516461 Maintenance...
Page 76: ...76 Maintenance Condensation and moisture in the heat pump cont 5516461 Maintenance...
Page 79: ...79 Parts lists type BWC 301 B Parts not shown type BWC 301 B cont 5516461 Components...
Page 88: ...88 Parts lists type BWC 301 B Hydraulics type BWC 301 B cont 5516461 Components...
Page 91: ...91 Parts lists type BW 301 B Parts not shown type BW 301 B cont 5516461 Components...
Page 100: ...100 Parts lists type BW 301 B Hydraulics type BW 301 B cont 5516461 Components...
Page 103: ...103 Parts lists type BWS 301 B Parts not shown type BWS 301 B cont 5516461 Components...