In conjunction with power-OFF: Load circuit (400 V~) and control circuit
(230 V~) on site
Type
Control circuit
(230 V~)
Cable cross-section
Power circuit (400 V~)
Cable cross-sec-
tion
Max. cable
length
BW 301.AS090
BW 302.AS090
WW 301.AS125
WW 302.AS125
5 x 2.5 mm
2
5 x 25 mm
2
40 m
BW 301.AS120
BW 302.AS120
WW 301.AS155
WW 302.AS155
5 x 2.5 mm
2
5 x 35 mm
2
40 m
BW 302.AS150
WW 302.AS200
5 x 2.5 mm
2
5 x 50 mm
2
40 m
BW 302.AS180
WW 302.AS250
5 x 2.5 mm
2
5 x 70 mm
2
with cable lug for
M8
40 m
BW 302.AS250
WW 302.AS300
5 x 2.5 mm
2
5 x 95 mm
2
with cable lug for
M8
40 m
Note
■ The control circuit must be supplied
with power without blocking by the
power supply utility, so a separate
power supply is required for the control
circuit.
■ A separate power connection for the
control circuit calls for the internal wir-
ing to be changed. This may only be
carried out by an electrician according
to the electrical wiring diagram.
■ The control circuit power supply and
the cable for the power-OFF signal can
be combined in one 5-core cable.