43
Circuit protection from load MCB 5F1 (observe the total current of max. 16 A)
Terminals
Function
Explanation
13X0
Circulation pump, evapora-
tor
Heat pump
Connection values
■ Max. output: 4000 W
■ Voltage:
400 V~/230 V~
■ Max. switching current: 9 A (AC3)
Connect on site.
13X5
Circulation pump,
Condenser
Heat pump
Connection values
■ Max. output: 4000 W
■ Voltage:
400 V~/230 V~
■ Max. switching current: 9 A (AC3)
Connect on site.
Circuit protection from load MCB 6F4 (observe the max. switching current of
9 A)
Terminals
Function
Explanation
21X1
Circulation pump, ground-
water
Heat yield
Groundwater option
Connection values
■ Max. output: 4000 W
■ Voltage:
400 V~/230 V~
■ Max. switching current: 9 A (AC3)
Connect on site.
Note
Fit the inspection switch upstream of the
circulation pump.
13X2
Safety pressure switch,
brine pressure/frost stat
Heat yield
Connect on site.
Insert jumper if no safety components
are installed.
Installation sequence
Overview of electrical connections
(cont.)
5848 246 GB
Installation