51
Terminals
Function
Explanation
8X1
Winding protection, com-
pressor 1
Connection values
■ Voltage:
24 VDC
Wired at the factory
8X3
High pressure switch, com-
pressor 1
Connection values
■ Voltage:
24 VDC
Wired at the factory
9X1
Winding protection, com-
pressor 2
Connection values
■ Voltage:
24 VDC
Wired at the factory
9X3
High pressure switch,
compressor 2
Connection values
■ Voltage:
24 VDC
Wired at the factory
13X6
MV control valve, liquid
Evaporator
Heat yield
Connection values
■ Max. output:
22 VA
■ Voltage:
24 VDC/0-10
Wired at the factory
18X2
Safety pressure switch
Low pressure
Heat pump
Connection values
■ Voltage:
24 VDC
Wired at the factory
Danger
All sensor leads and 0-10 V sig-
nal leads must be shielded with
copper braiding and have a min-
imum cross-section of 0.5 mm
2
.
Specified lead type: CV.
Installation sequence
Overview of electrical connections
(cont.)
5848 246 GB
Installation