42
Overview of electrical connections
Terminal strip, external connections
400 V~/230 V~ components
External connections
Terminals
Function
Explanation
12X0
Potential-free operating
message, compressor 1
Contact closed during oper-
ation
Connection values
■ Max. voltage: 250 V~
■ Max. switching current: 4 A (AC1)
Connect on site.
12X2
Potential-free operating
message, compressor 2
Contact closed during oper-
ation
Connection values
■ Max. voltage: 250 V~
■ Max. switching current: 4 A (AC1)
Connect on site.
12X4
Potential-free operating
message, compressor 3
Contact closed during oper-
ation
Connection values
■ Max. voltage: 250 V~
■ Max. switching current: 4 A (AC1)
Connect on site.
12K8/11;14 Potential-free central alarm,
heat pump
Contact open when there is
a fault
Connection values
■ Max. voltage: 250 V~
■ Max. switching current: 4 A (AC1)
Connect on site.
Installation sequence
Overview of electrical connections
(cont.)
5848 246 GB