90
19. Correct adjustment of heating curve and set temperature constants
The heating curve is optimally adjusted if the standard room temperature results
from the heating curve alone. Consequently, the temperature correction factor
must be
0
when adjusting the heating curves. In addition, in the detailed heating
circuit view, the set room temperature must be set to a value which is identical
to the standard room temperature.
The standard room temperature is the average set or intended room tempera-
ture.
20. Correct setting of parameter "Factor set room curve/heating curve change"
This factor determines the relationship between the room temperature adjust-
ment and the necessary modification to the flow temperature.
Theory:
This factor is required as the room temperature is always below the flow
temperature.
Optimal factor adjustment: A calculation needs to be made to find out the value
by which the flow temperature needs to be raised in order to achieve a 1 °C
higher room temperature.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5848 246 GB