36
Required parameter settings for DHW heating
Set the required parameters during com-
missioning; see from page 108.
Parameter
Setting
"System definition"
■
"System scheme 7000"
"0"
/
"2"
/
"4"
/
"6"
/
"8"
/
"10"
DHW heating:
"Time program DHW"
Set time program (see oper-
ating instructions)
"Time prog. DHW circ."
Set time program (see oper-
ating instructions)
"DHW"
■
"Enable booster heaters for DHW heating 6014" "1"
■
"Enable electric heaters for DHW heating 6015"
"1"
"External heat source"
■
"Enable external heat source for DHW heating
7B0D"
"0"
Integration of the two-stage version in the system examples
Note
■ A two-stage heat pump comprises the
heat pump stage 1 (type BW 301.A or
WW 301.A) and the heat pump stage
2 (type BWS 301.A).
■ Connect return DHW cylinder only to
heat pump stage 1.
■ The partial scheme can be integrated
into the system examples via the inter-
faces indicated.
Preparing for installation
DHW heating
(cont.)
5600 161 GB
Summary of Contents for BW 01.A06
Page 121: ...121 Opening the shield Troubleshooting Repairs cont 5600 161 GB Service ...
Page 166: ...166 5600 161 GB ...
Page 167: ...167 5600 161 GB ...