83
Central fault message
223.1
L1
230 V~, 0.5 A
N
223.2
A
A
Terminals on extension PCB
Plug
sXF
Terminals
Function
Explanation
224.2
2.
Primary pump for heat pump
stage 2 (if installed)
Connection values
■ Output: 200 W
■ Voltage: 230 V~
■ Max. switching current: 4(2) A
Connect on site.
224.3
2.
Secondary pump for heat
pump stage 2 (if installed)
Connection values
■ Output: 130 W
■ Voltage: 230 V~
■ Max. switching current: 4(2) A
Connect on site.
224.4
r
2.
Control of instantaneous
heating water heater,
stage 2
Connection values
■ Output: 10 W
■ Voltage: 230 V~
■ Max. switching current: 4(2) A
Connect on site.
224.5
2.
Circulation pump for cylinder
heating (on the heating
water side) for heat pump
stage 2 (if installed)
Connection values
■ Output: 130 W
■ Voltage: 230 V~
■ Max. switching current: 4(2) A
Connect on site.
Installation sequence
Electrical connections
(cont.)
5600 161 GB
Installation