External heat source
External heat source parameters
Setting
"External heat source"
Ó
"Enable external heat source 7B00"
"1"
With circulation pump for DHW reheating:
"External heat source"
Ó
"Enable booster heaters for DHW heating
6014"
"1"
Swimming pool water heating
Parameters for swimming pool water heating
Setting
"System definition"
Ó
"External extension 7010"
"1"
"System definition"
Ó
"Swimming pool 7008"
"1"
Heat pump cascade
Cascade via external extension H1
Parameter
Setting
Lead appliance
Lag heat pump
"System definition"
Ó
"System scheme 7000"
"0"
to
"10"
"11"
"System definition"
Ó
"External extension 7010"
"1"
"0"
"System definition"
Ó
"Cascade control 700A"
"1"
"0"
"System definition"
Ó
"Number of lag heat pumps in
cascade 5735"
"1"
to
"3"
–
"System definition"
Ó
"Output lag heat pump 700B"
"0"
to
"255"
–
"System definition"
Ó
"Use of heat pump in a cas-
cade 700C"
"0"
to
"3"
–
"System definition"
Ó
"Flow temperature for external
demand 730C"
–
"0"
to
"700"
(
≙
0 to 70 °C)